Transformer Oil Testing

Sl.No.

Name of the Test

Equipment used

1Dissolved Gas Analysis (DGA) Test
To detect and quantify fault gases dissolved in Transformer oil so as to identify incipient faults in Transformers.
Gas Chromatograph with Head Space Auto Sampler
Make: Perkin Elmer, U.S.A . Model : ARNEL CLARUS 580.
2Furan Analysis Test
To determine the deterioration, ageing state and the condition of the solid insulation in Transformers.
High Performance Liquid Chromatograph (HPLC)
Make : Waters India Ltd.
3Water content test
To determine the dissolved water present in the Transformer Oil.
Fully Automatic coulometric Titration Kit
Make : Metrohm Devices/Switzerland.
4Tan delta and Resistivity test
To determine the Resistivity & Tan Delta of the Transformer oil.
Automatic Tan delta and Resistivity test Kit
Make : ELTEL /Bangalore.
5Acidity Test
To determine the acidity in the Transformer Oil.
Automatic Acidity test kit
Make : Spectra Lab Instruments.
6Break Down Voltage (BDV) test
To determine the dielectric strength of the Transformer Oil.
Fully automatic BDV kit capable of testing up to 100 KV
Make : Megger/UK.
7Flash Point Test
To determine the Flash Point of the Transformer Oil.
Fully Automatic Pensky Martens closed cup test kit
Make : ANTON PAAR. (Temp. Measurement up to 350 ˚C)
8Interfacial Tension Test
To determine the Interfacial Tension of Transformer Oil ;
Fully automatic IFT test kit
Make : KRUSS/ Germany.
9Sludge Test
To Determines the sludge or sediments present in the Transformer Oil.
Chemical sludge test

Testing Facilities At R & D, Chennai.

Sl.No.Name of the TestEquipment used
1Measurement of Tan delta and Capacitance at 10 KV for Power, Auto and Instrument Transformers.(a) Insulation Analyser kit
Make : Doble /USA. (b) Capacitance and Dissipation factor test kit
Make : ELTEL/ Bangalore.
2Measurement of Transformer Excitation current at 10 KV.Insulation Analyser kit
Make : Doble/ USA.
3Measurement of Transformer Turns Ratio at 10 KVInsulation Analyser kit
Make: Doble/ USA
4Measurement of Transformer Leakage ReactanceInsulation Analyser kit
Make: Doble/ USA
5Measurement of Leakage current in High Voltage Surge Arresters60 KV Testing Transformer and accessories
6Measurement of soil Resistivity and Earth Resistance of sub-station Earthing SystemElectronic Earth Megger
Make : GEOHM/U.K.
7Measurement of Insulation Resistance and PI value at 5 KV.5KV Insulation Tester
Make : Megger/U.K.
8Measurement of power quality
Class A Harmonic Analyser
Make : Dranetz /USA , Model: Power Visa
9Sweep Frequency Response Analyser

Transformer core and winding condition analyzing kit.
Make : MEGGER/SWEDEN ,

Model: FRAX-101

10Frequency Domain Spectroscopy/ Dielectric Frequency Response Analyser
Transformer insulation moisture, Bushing and CT Tan delta/Moisture measurement kit.
Make : MEGGER/ SWEDEN.

Model :IDAX 300S

Note : All the above testing facilities can be utilised by private agencies also on chargeable basis

TESTING FACILITIES AT R & D, CHENNAI

 Contact Person and address
Chief Engineer/ IC,R&D/ Chennai
Superintending Engineer/ R&D/ Chennai044-28591236
Executive Engineer/R&L/Chennai044-28520131- Extn-2402
Executive Engineer/R&D Projects/ Chennai044-28520131- Extn-2487
Assistant Executive Engineer/R&D/Chennai044-28520131- Extn-2822, 2823
R&D Lab/Chennai044 - 28414912, 28520131 Ext - 2454, 2435
Oil Testing Lab/Trichy0431-2465177 Cell:9445853452, 9445853453
Oil Testing Lab/Coimbatore0422-2493262 Cell:9445851309, 9445851311

Save-energy1 Energy / Electricity Saved is Energy ProducedSave-energy2 Energy conservation, a key to sustainable developmentSave-energy3 Energy is in limited supply, Use it wiselySave-energy4 Turn off lights and equipments when not in useSave-energy5 Save energy for benefit of self and nation   Save-energy1 Install RCD to safeguard life from Electrical Accidents